Skip to main content

Modbus

Overview

The Modbus plugin collects Discrete Inputs, Coils, Input Registers and Holding Registers via Modbus TCP or Modbus RTU/ASCII.

Configuration

[[inputs.modbus]]
## Connection Configuration
##
## The plugin supports connections to PLCs via MODBUS/TCP or
## via serial line communication in binary (RTU) or readable (ASCII) encoding
##
## Device name
name = "Device"

## Slave ID - addresses a MODBUS device on the bus
## Range: 0 - 255 [0 = broadcast; 248 - 255 = reserved]
slave_id = 1

## Timeout for each request
timeout = "1s"

## Maximum number of retries and the time to wait between retries
## when a slave-device is busy.
# busy_retries = 0
# busy_retries_wait = "100ms"

# TCP - connect via Modbus/TCP
controller = "tcp://localhost:502"

## Serial (RS485; RS232)
# controller = "file:///dev/ttyUSB0"
# baud_rate = 9600
# data_bits = 8
# parity = "N"
# stop_bits = 1
# transmission_mode = "RTU"


## Measurements
##

## Digital Variables, Discrete Inputs and Coils
## measurement - the (optional) measurement name, defaults to "modbus"
## name - the variable name
## address - variable address

discrete_inputs = [
{ name = "start", address = [0]},
{ name = "stop", address = [1]},
{ name = "reset", address = [2]},
{ name = "emergency_stop", address = [3]},
]
coils = [
{ name = "motor1_run", address = [0]},
{ name = "motor1_jog", address = [1]},
{ name = "motor1_stop", address = [2]},
]

## Analog Variables, Input Registers and Holding Registers
## measurement - the (optional) measurement name, defaults to "modbus"
## name - the variable name
## byte_order - the ordering of bytes
## |---AB, ABCD - Big Endian
## |---BA, DCBA - Little Endian
## |---BADC - Mid-Big Endian
## |---CDAB - Mid-Little Endian
## data_type - INT16, UINT16, INT32, UINT32, INT64, UINT64, FLOAT32-IEEE, FLOAT64-IEEE (the IEEE 754 binary representation)
## FLOAT32 (deprecated), FIXED, UFIXED (fixed-point representation on input)
## scale - the final numeric variable representation
## address - variable address

holding_registers = [
{ name = "power_factor", byte_order = "AB", data_type = "FIXED", scale=0.01, address = [8]},
{ name = "voltage", byte_order = "AB", data_type = "FIXED", scale=0.1, address = [0]},
{ name = "energy", byte_order = "ABCD", data_type = "FIXED", scale=0.001, address = [5,6]},
{ name = "current", byte_order = "ABCD", data_type = "FIXED", scale=0.001, address = [1,2]},
{ name = "frequency", byte_order = "AB", data_type = "UFIXED", scale=0.1, address = [7]},
{ name = "power", byte_order = "ABCD", data_type = "UFIXED", scale=0.1, address = [3,4]},
]
input_registers = [
{ name = "tank_level", byte_order = "AB", data_type = "INT16", scale=1.0, address = [0]},
{ name = "tank_ph", byte_order = "AB", data_type = "INT16", scale=1.0, address = [1]},
{ name = "pump1_speed", byte_order = "ABCD", data_type = "INT32", scale=1.0, address = [3,4]},
]